+358 404 844 684
sale@labscand.com
+358 404 844 684
sale@labscand.com

Labscand DS3200-3250 UPS

Häiriöttömän sähkönsyötön ratkaisuja Labscand Labscand DS3200-3250 edustaa tornissa olevat järjestelmät 200-250 kVA. Järjestelmät toimivat jännitteen kaksoismuuttajana.

Labscand DS3200-3250 UPS

Kolmivaiheinen häiriöttömän sähkönsyötön ratkaisut teholtaan 200-250 kVA,  tyyppi Online

MODEL
DS3200
DS3250
Power (kVA)
200
250
INPUT
Voltage
380/400 VAC 3P + N + G   ± 20%  (415 VAC +15%, – 25% optional)
Frequency
50Hz / 60Hz, ± 5%
Power factor
≥ 0.99
(THDI) (*)
≤ 3%
By-pass voltage
380/400 VAC 3P + N , 4 Wires, ± 10%
Voltage distortion
≤ 10%
Protection
Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
OUTPUT
Power (kW)
180
225
Power factor
0,9
Voltage
380/400 VAC 3 Phase + N ,  ± 1% (415 optional)
Frequency
50Hz / 60Hz
Frequency tolerance
Line synchronized: ± 2% / Free running: ± 0,1%
Efficiency
up to 95%
Crest factor
3:1
Overload protection
100% – 125% load: 10 min,  125% – 150% load: 1 min, –  > 150% load: by pass
Other protections
Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
Voltage THD
< 3% (at 100% linear load)
BATTERIES
Type
VRLA AGM / GEL / NiCd
Nominal voltage
± 360 VDC
Float / End of discharge voltage
± 405 VDC   /  ± 300 VDC
Battery cabinet
External
Battery ambient temperature
25ºC
Protections
3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic testing
Standard every 72 hours (adjustable)
GENERAL
Standards
EN62040-1, EN62040-2, EN62040-3
User interface
TFT panel, 5 vector buttons, Buzzer,
Indicators
P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced
Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication
2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs
EPO input, Interactive battery panel input, Genset input
Genset kit
Standard (programmable)
Software
Standard T-Mon UPS Management Software (3 clients + 1 server management)
Alarm logging
Standard: with time & date 512 events
Protections
Power module over-temperature, Over current, Temperature high alarm
Temperature range
0ºC – 40ºC
Protection degree
IP20
Relative humidity
90% max. (non-condensing)
Altitude
< 1000m. above sea level
Acoustic noise
< 68 dBA
OPTIONS
Different input / output voltage
Please ask
Transformer
Galvanic isolation transformer at the input & output
Software
T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Adaptors
SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP ,GSM/GPRS Modem, Comport multiplexer
Parallel operation
up to 8
(*) Depending on power and input/output conditions

Labsсand OY has CE certificate for the company’s products:

EC serteficate UPS Labscand DS300

Voitto

Järjenmukainen menetelmä

Parhaiden hinnan ja ominaisuuden osalta laitteiden valinta suunnittelutehtäväsi mukaan

Sertifioidut laitteet

Vaatimustenmukaisuustodistukset ja luvat käyttämiseen erittäin tärkeissä kohteissa

Ratkaisut “avaimen käteen”

Yksikkökohtaiset ratkaisut ja tarvittava kokoonpano

Yhteistyön joustavat ehdot

Suhteiden tilaajaan rakentaminen saattaa yhteisiin tavoitteisiin ja molemmin puolin edulliseen yhteistyöhön

Onko lisää kysymyksiä? Jätä puhelinnumerosi ja asiantuntija ottaa yhteyden sinuun!