All Labscand DS310SH-315SH-320SH UPS use transformerless topology and perfome high efficiency up to 94%, cold start function, 3 level battery protection and many other advanced features.
MODEL
|
DS310SH
|
DS315SH
|
DS320SH
|
---|---|---|---|
Power (kVA)
|
10
|
15
|
20
|
INPUT
|
|||
Voltage
|
380/400 VAC 3P + N + G ± 20% (415VAC +15%, -25% optional )
|
||
Frequency
|
50Hz / 60Hz, ± 5%
|
||
Power factor
|
≥ 0.99
|
||
THDI (at 100% load)
|
≤ 4% (depends on mains input conditions)
|
||
By-pass voltage
|
380/400 VAC 3 Phase + N , 4 Wires, ± 10%
|
||
Voltage distortion
|
≤ 10%
|
||
Protection
|
Fuses, Voltage & Frequency Tolerance
|
||
OUTPUT
|
|||
Power (kW)
|
9
|
13,5
|
18
|
Power factor
|
0,9
|
||
Voltage
|
380/400 VAC 3P + N , ± 1% (415 VAC optional )
|
||
Frequency
|
50Hz / 60Hz
|
||
Frequency tolerance
|
Line synchronized: ± 2% / Free running: ± 0,1%
|
||
Efficiency
|
94,5%
|
94%
|
93%
|
Crest factor
|
3:1
|
||
Overload protection
|
100% – 125% load: 10 min, 125% – 150% load: 1 min, – > 150% load: by pass
|
||
Protection
|
Fuses,Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
|
||
Voltage THD
|
< 3% (at 100% linear load)
|
||
BATTERIES
|
|||
Type
|
VRLA AGM / GEL / NiCd
|
||
Number of batteries
|
60 (± 30) batteries
|
||
Float charging voltage
|
± 405 VDC (adjustable)
|
||
End of discharge voltage
|
± 300 VDC (adjustable)
|
||
Battery cabinet
|
External (attached cabinet at the bottom of UPS)
|
||
Battery ambient temperature
|
25°C
|
||
Battery protection
|
3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
|
||
Automatic battery test
|
Standard: every 72 hours (adjustable)
|
||
GENERAL
|
|||
Standards
|
EN62040-1, EN62040-2, EN62040-3
|
||
User interface
|
4 lines LCD panel, Mimic leds, 5 vector buttons, buzzer
|
||
Indicators
|
P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
|
||
Advanced
|
Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
|
||
Communication
|
RS232 serial port, 4 standard DRY contact alarm relays
|
||
Inputs
|
EPO input
|
||
Genset kit
|
Standard (programmable)
|
||
Software
|
Standard T-Mon UPS Management Software (3 clients + 1 server management)
|
||
Alarm logging
|
Standard: with time & date 512 events
|
||
Protection
|
Power module over temperature, Over current, Temperature high alarms
|
||
Operating temperature
|
0°C – 40°C
|
||
Protection degree
|
IP20
|
||
Relative humidity
|
90% max. (non-condensing)
|
||
Altitude
|
< 1000m. above sea level
|
||
Acoustic noise
|
< 55 dBA
|
< 57 dBA
|
< 61 dBA
|
OPTIONS
|
|||
Different input / output voltage
|
Please ask
|
||
Adaptors
|
SNMP, MODBUS, RS485, Remote panel
|
||
Software
|
T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
|
||
Parallel operation
|
Not Available
|
Labsсand OY has CE certificate for the company’s products: