500 kVA 3Ph online UPS system
MODEL
|
DS3500
|
---|---|
Power (kVA)
|
500
|
INPUT
|
|
Voltage
|
380/400 VAC 3P + N + G ± 20% (415 VAC +15%, – 25% optional)
|
Frequency
|
50Hz / 60Hz, ± 5%
|
Power factor
|
≥ 0.99
|
(THDI) (*)
|
≤ 3%
|
By-pass voltage
|
380/400 VAC 3P + N , 4 Wires, ± 10%
|
Voltage distortion
|
≤ 10%
|
Protection
|
Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicator
|
OUTPUT
|
|
Power (kW)
|
270
|
Power factor
|
0,9
|
Voltage
|
380/400 VAC 3 Phase + N , ± 1% (415 optional)
|
Frequency
|
50Hz / 60Hz
|
Frequency tolerance
|
Line synchronized: ± 2% / Free running: ± 0,1%
|
Efficiency
|
up to 95%
|
Crest factor
|
3:1
|
Overload protection
|
100% – 125% load: 10 min, 125% – 150% load: 1 min, – > 150% load: by pass
|
Other protections
|
Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
|
Voltage THD
|
< 3% (at 100% linear load)
|
BATTERIES
|
|
Type
|
VRLA AGM / GEL / NiCd
|
Nominal voltage
|
± 360 VDC
|
Float / End of discharge voltage
|
± 405 VDC / ± 300 VDC
|
Battery cabinet
|
External
|
Battery ambient temperature
|
25ºC
|
Protections
|
3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
|
Automatic testing
|
Standard every 72 hours (adjustable)
|
GENERAL
|
|
Standards
|
EN62040-1, EN62040-2, EN62040-3
|
User interface
|
TFT panel, 5 vector buttons, Buzzer,
|
Indicators
|
P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
|
Advanced
|
Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
|
Communication
|
2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
|
Inputs
|
EPO input, Interactive battery panel input, Genset input
|
Genset kit
|
Standard (programmable)
|
Software
|
Standard T-Mon UPS Management Software (3 clients + 1 server management)
|
Alarm logging
|
Standard: with time & date 512 events
|
Protections
|
Power module over-temperature, Over current, Temperature high alarm
|
Temperature range
|
0ºC – 40ºC
|
Protection degree
|
IP20
|
Relative humidity
|
90% max. (non-condensing)
|
Altitude
|
< 1000m. above sea level
|
Acoustic noise
|
< 68 dBA
|
OPTIONS
|
|
Different input / output voltage
|
Please ask
|
Transformer
|
Galvanic isolation transformer at the input & output
|
Software
|
T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
|
Adaptors
|
SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), USB Alarm Logger, TCP/IP ,GSM/GPRS Modem, Comport multiplexer
|
Parallel operation
|
up to 8
|
(*) Depending on power and input/output conditions
|